Basic Functions |
Range |
Best Accuracy |
Model |
|
UT523A |
Earth resistance |
0.00Ω~19.99Ω |
±(2%+5) |
20.0Ω~199.9Ω |
±(2%+5) |
200Ω~1999Ω |
±(2%+5) |
2.00kΩ~19.99kΩ |
±(2%+5) |
20.0kΩ~210.0kΩ |
±(2%+5) |
Soil resistivity |
0.00Ωm~99.99Ωm |
Decided by measuring precision of R: (ρ=2πaR a:1 m~100m, π=3.141) |
100.0Ωm~999.9Ωm |
1000Ωm~9999Ωm |
10.00kΩm~99.99kΩm |
100.0kΩm~999.9kΩm |
1000kΩm~9000kΩm |
Earth voltage |
AC 0.00~750V |
±(2%+5) |
Testing resistance |
128Hz/111Hz/105Hz/94Hz(AFC) |
√ |
Features |
Measuring method |
Earth resistance: rated current pole changing method with Max 20mA measuring current; |
√ |
soil resistivity: quadrupole method (Wen-Na method ); |
earth voltage: average rectifier (between P(S) and ES interfaces) |
Short-circuit testing current |
AC 30mA max |
√ |
Open-circuit testing voltage |
AC 40V max |
√ |
Auto range |
|
√ |
Distance between electrodes |
1m~200m can be set. |
√ |
Testing voltage waveform |
Sine wave |
√ |
Line voltage |
Measure when the voltage is below 750V AC |
√ |
Low battery indicator |
≤7.5V |
√ |
Data hold |
|
√ |
Alarm function |
|
√ |
RS232 interface |
|
√ |
Withstand voltage |
AC 3700V/rms(between circuit and case) |
√ |
LCD backlight |
|
√ |
Data storage |
300 groups |
√ |
Auxiliary earth resistance test |
0.00KΩ~30kΩ(100R+rC<50kΩ, 100R+rP<50kΩ) |
√ |
Overload protection |
Earth resistance measurement: input 280V AC between C(H) and E, P(S) and ES for 3s |
√ |
Interference test |
Auto identify interference signals, when interference voltage is higher than 5V, the symbole NOISE is displayed. |
√ |
Measuring time(s) |
More than 5000 times (perform short circuit test once, and again after 30s) |
√ |
Insulation resistance |
Above 20MΩ (500V between circuit and case) |
√ |